EasyManuals Logo

Siemens FD20 User Manual

Siemens FD20
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
3BPlanning
25BParameter sets: Neural fire detector
4
63 |
138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
Only select this parameter set if high sensitivity is required and no deceptive
phenomena (visible aerosols) can be expected.
No.
Name
Response time [s]
Sensitivity
To open fire/smoldering fire
[%/m]
0
1
Universal 50 2.3 / 8.0
2 Robust 80 2.3 / 8.0
1 Universal 50 2.3 / 8.0
3
2
Sensitive 30 1.6 / 5.6
4
3
Universal Fast 8 2.3 / 8.0
5 Super Sensitive 12 1.0 / 1.5
6 Ultra Sensitive 12 0.35 / 0.5
1
Delivery status; can only be selected in collective mode and MS8 mode.
2
Default status in AnalogPLUS mode as DO1131A
3
Can only be selected in AnalogPLUS mode
Parameter sets 0…5 meet the criteria of standard EN 54-7.
Parameter set 5 meets the criteria of standard EN 54-27. You will find more
information in documents A6V10446712 and A6V10427924. See 'Applicable
documents [➙ 9]' chapter.

Table of Contents

Other manuals for Siemens FD20

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FD20 and is the answer not in the manual?

Siemens FD20 Specifications

General IconGeneral
BrandSiemens
ModelFD20
CategorySecurity Sensors
LanguageEnglish

Related product manuals