6 APPENDIX
FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL | APPENDIX C
Adjusting the Alarm
Threshold When a New
Zeus is Uploaded After FireFinder-XLS checks that the actual ID of a device with IEC agrees with Zeus,
it adjusts the detectors alarm threshold according to the data stored. The first
adjustment occurs after 100 hours of data accumulation. In the case of power cycling
or resetting, adjustments begin within 90 seconds.
If a detector with IEC reports an alarm condition before the detectors alarm thresh-
old is adjusted, the alarm delays until the alarm threshold is adjusted. If the device
continues to report an alarm condition once its alarm threshold is adjusted, the alarm
reports.
If the Zeus and the device ID do not agree, the IEC for that device does not activate
until the trouble condition is removed from the system and the panel is reset.
Ongoing Adjustments of
the Alarm Threshold Environmental conditions usually cause a small change in the analog voltage over a
long period of time. At regular intervals FireFinder-XLS collects analog data for each
detector with IEC and adjusts the alarm threshold accordingly. FireFinder-XLS adjusts
for both up and down changes in the analog voltage. In addition, if system power is
lost, FireFinder-XLS adjusts the alarm thresholds as needed by using stored data.
IEC Trouble Conditions A trouble condition involving the IEC may be annunciated by the FireFinder-XLS PMI/
PMI-2/PMI-3 as:
PRE-DIRTY ANALOG VOLT. REACHED
OR
IEC LIMIT REACHED. SERVICE REQ
The trouble conditions shown above are annunciated on a detector-by-detector basis
as each detector is checked.
FireFinder-XLS annunciates a trouble condition for a detector when its alarm thresh-
old reaches a predetermined limit. The operator should acknowledge the trouble,
clean the detector if possible, and reset the control panel. If the detector is not
cleaned, the control panel annunciates this trouble condition after every panel reset
until the detector is cleaned.

Table of Contents

Other manuals for Siemens FIREFINDER-XLS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FIREFINDER-XLS and is the answer not in the manual?

Siemens FIREFINDER-XLS Specifications

General IconGeneral
BrandSiemens
ModelFIREFINDER-XLS
CategoryControl Panel
LanguageEnglish

Related product manuals