12 APPENDIX
FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL | APPENDIX E
NOTES
1. HTRI-R input must be programmed in
Zeus as trouble causing.
2. HTRI-R output must be programmed in
Zeus to transfer on loss of AC Mains.
3. All wiring supervised except as noted.
4. For Remote Station, provide 60 hour
battery capacity.
5. In Zeus, program PSC-12 User Relay 1
to activate on any supervisory.
6. All wiring Power Limited to NFPA 70
per NEC 760.
P1 - DC POWER
P3 - AC MONITOR
(SEE NOTE 2)
P3 -ACMONITOR
(SEE
NOTE 2)
RELAY NC
RELAY C
RELAY NO
(RED)
TELCO 1 RING (GREEN)
TELCO 1 TIP (RED)
HOUSE 1 TIP (GRAY)
HOUSE 1 RING (BROWN)
HOUSE 2 RING (BROWN)
HOUSE 2 TIP (GRAY)
TELCO 2 TIP (RED)
TELCO 2 RING (GREEN)
TELCO 2 RING (GREEN)
(BLK)
SILENT KNIGHT 5230
(PROGRAMMING)
SILENT KNIGHT 5230
(PROGRAMMING)
P2 - CHANNEL INPUTS
(GRY)
(YLW)
(VIO)
(ORN)
(BLU)
(RED)
(RED)
(GRN)
(BRN)
(YLW)
(ORN)
(RED)
(BRN)
(BLK)
(WHT)
SUPERVISED
TO RJ31X
TO RJ31X
SILENT KNIGHT
MODEL NO. 5129
PSC-12
HTRI-R
UL LISTED
EOL DEVICE
470 OHM, 1/4W
(P/N 140-820164)
UL LISTED
EOL DEVICE
470
OHM, 1/4W
(P/N
140-820164)
*
UL LISTED
EOL DEVICE
4.7K, 1/2W, 5%
(P/N 140-820388)
*
UL LISTED
EOL DEVICE
4.7K,
1/2W, 5%
(P/N
140-820388)
*
19
24
18
13
TB2
1
2
3
4
5
8
7
6
P5
1
1
1
+
_
2
6
12
7
12
34
TB1
TB3
P4
1
+
+
_
_
2
H
N
GND
P9
P12
TB4
Electrical Ratings Supervisory 18-40 VDC
60mA
Alarm 18-40 VDC
130mA