EasyManua.ls Logo

Siemens FM 450-1 - UKCA Approval; Explosion Protection

Siemens FM 450-1
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.3.4 UKCA approval
DEKRA 21UKEX0018 X
Importer UK:
Siemens plc
Manchester M20 2UR
12.3.5 Explosion protection
ATEX approval DEKRA 21ATEX0010 X
Type examination certi󹪝cate number DEKRA 21ATEX0010 X
Standards EN IEC 60079-0
EN 60079-7
Marking II 3 G Ex ec IIC T4 Gc
The certi󹪝cate is valid for the "DEKRA 21ATEX0010 X (https://support.industry.siemens.com/cs/
document/109475140)" products listed in the certi󹪝cate.
Special conditions
The device may only be used in areas with a pollution degree of no more than 2 according to
EN 60664‑1.
The modules must be installed in a suitable enclosure which provides a degree of protection
of at least IP54 in accordance with EN 60079‑7, taking into account the ambient conditions
of use.
Measures must be taken to prevent exceeding the rated voltage by more than 119 V of
transient disturbance voltages.
IECEx approval IECEx DEK 21.0008X
Certi󹪝cate number IECEx DEK 21.0008X
Standards IEC 60079-0
IEC 60079-7
Marking Ex ec IIC T4 Gc
The certi󹪝cate is valid for the "IECEx DEK 21.0008X (https://support.industry.siemens.com/cs/document/
109795939)". products listed in the certi󹪝cate.
Technical Data
12.3 Standards and approvals
Counter module FM 450-1
104 Equipment Manual, 03/2022, A5E03648739-AC

Table of Contents

Related product manuals