No. Meaning
203 Value too great for the evaluation of the signals
204 Value too great for the input lter of the 24V count signals
205 Value too great for the input lters of the digital inputs
206 Reversing the direction not permitted
207 Value too great for the behavior of digital output 1Q0 (2Q0)
208 Value too great for the behavior of digital output 1Q1 (2Q1)
209 Pulse duration wrong or too long
211 Wrong mode selected
212 No gate or both gates specied
215 When assigning the process interrupt "Reaching the comparison value in the up and/or down
count direction" parameters a dierent count direction was specied than the parameter assign‐
ment for the behavior of the outputs "Output active for on pulse duration in up and/or down
direction". The directions must match.
216 Gate control interrupts are only possible for modes with gate control
217 No interrupt on reaching the comparison values is permitted for behavior of the digital outputs
"active between comparison value and overow" or "active between comparison value and un‐
derow".
How are data errors acknowledged?
Correct the values for the parameters to comply with the specications. Transfer the corrected
set of parameters to the FM 450-1 again. This again checks the parameters and deletes the data
error in DB 1.
11.5 Operator error
When do operator errors occur?
Operator errors occur if you operate the module incorrectly by specifying the wrong control
signals.
Where are operator errors indicated?
FC CNT_CTRL enters the operator error numbers in DB1. You can access this data word via the
variable name "OT_ERR_B" in your program.
Errors and diagnostics
11.5 Operator error
Counter module FM 450-1
96 Equipment Manual, 03/2022, A5E03648739-AC