Byte Bit Meaning Remark Event no.
8 0 Signal A - faulty channel 1 8:x:B0
1 Signal B - faulty channel 1 8:x:B1
2 Signal N faulty channel 1 8:x:B2
4 5.2V encoder supply faulty channel 1 8:x:B4
9 Reserved
10 0 Signal A - faulty channel 2 8:x:B0
1 Signal B - faulty channel 2 8:x:B1
2 Signal N faulty channel 2 8:x:B2
4 5.2V encoder supply faulty channel 2 8:x:B4
11 Reserved
How does the diagnostic text appear in the diagnostic buer?
If you want to enter the diagnostic message in the diagnostic buer, you must call the SFC 52
(Enter user-specic message in the diagnostic buer" in the user program. The event number of
the diagnostic message in each case is specied in the input parameter EVENTN. The interrupt
is entered in the diagnostic buer with x=1 as incoming and x=0 as outgoing. The diagnostic
buer contains the relevant diagnostic text in the "Meaning" column as well as the time of the
entry.
Default setting
The diagnostic interrupt is disabled in the default setting.
11.4 Data error
When do data errors occur?
If new parameters are transferred to the module, the FM 450-1 checks these parameters. If
errors occur during this check, the module reports these data errors.
Wrong parameters are not accepted by the module.
Where are data errors indicated?
The FC CNT_CTRL enters the data errors in DB1 with the error numbers. You can access this data
word via the variable name "DA_ERR_W" in the user program The following table shows the
numbers of the data errors and the signicance of these errors.
Table 11-3 Data error numbers and their signicance
No. Meaning
0 No fault
201 Value too great for receiver selection
202 Value too great for the diagnostics of the pair of signals
Errors and diagnostics
11.4 Data error
Counter module FM 450-1
Equipment Manual, 03/2022, A5E03648739-AC 95