A
*
B
*
N
*
DC24V
11
12
13
14
16
A
*
B
*
N
*
DC24V
23
24
25
26
28
1 M
1 M
Front connector
Shield on
shied attachment
Shield on
housing
Counter 1
Counter 2
Shield on
shield attachment
Shield on
housing
Figure 4-3 Incremental 24 V encoder connection
• Use exible cables with cross sections of 0.25 to 1.5 mm
2
.
Note
If the encoder is supplied via the module, the cable cross section must be selected large
enough for sucient voltage to be applied to the encoder via the cable in spite of a drop in
voltage. This applies in particular in the case of incremental 5 V encoders.
• A wire end ferrule is not required. If you use wire end ferrules, they must be of the type
without insulating collars in compliance with DIN 46228 Form A, short type!
Wiring
4.3 Wiring Front Connectors
Counter module FM 450-1
Equipment Manual, 03/2022, A5E03648739-AC 33