Behavior of the outputs
For the two outputs you can set one of six possible responses to reaching the comparison value.
The various options are shown in the following table.
Digital output parameter
assignment
Behavior of the outputs
Disable
Underflow
Comparison value
Overflow
The output remains deactivated and is not aected by the comparison value, zero crossing,
overow, and underow events.
Active between compari‐
son value and overow
Underflow
Comparison value
Overflow
The output is enabled when the counter is within the range between comparison value n and
overow. The output is activated by setting the counter to a value between the comparison value
and overow.
Active between compari‐
son value and overow
Underflow
Comparison value
Overflow
The output is activated when the counter is within the range between comparison value and
underow. The output is activated by setting the counter to a value between the comparison
value and underow.
Active for "pulse duration"
when the comparison val‐
ue is reached in up direction
t
Underflow
Comparison value
Overflow
The output is activated when the comparison value is reached in the up counting direction for the
time the pulse lasts.
Active for "pulse duration"
when the comparison val‐
ue is reached in down di‐
rection
t
Underflow
Comparison value
Overflow
The output is activated when the comparison value is reached in the down count direction for the
time the pulse lasts.
Active for "pulse duration"
when comparison value is
reached in up or down di‐
rection
t
t
Underflow
Comparison
value
Overflow Overflow
Underflow
Comparison
value
Up
Down
The output is activated when the comparison value is reached for the time the pulse lasts, irre‐
spective of the counting direction.
A shaded in area in the table signies: The output is active.
t = pulse duration
Modes, settings, parameters and commands
8.8 Setting: Behavior of the digital outputs