1.4.3 Sockets for FCnet/C-WEB circuits (7, 8)
The 3-pole connectors for the FCnet/C-WEB connection are supplied with the fiber
network module.
The total cable length of the electrical FCnet/C-WEB connections (copper cable) in
the optical network must not exceed 3300 ft.
Connection bush A1/B1
Pin Designation Description
3 B1 FCnet/C-WEB circuit 1 (-)
2 NC Do not use
1 A1 FCnet/C-WEB circuit 1 (+)
Admissible cable cross-section: 16...28 AWG
Connection bush A2/B2 (7, 8)
Pin Designation Description
3 B2 FCnet/C-WEB circuit 2 (-)
2 NC Do not use
1 A2 FCnet/C-WEB circuit 2 (+)