Fiber network module FN2006 / FN2007
1
Technical data
14
Siemens Industry, Inc. A6V10315048_b_en_US
Building Technologies Division 01/13/2012
1.6 Technical data
Supply input Input voltage DC 24 V
Decentralized installation Shielded supply cable (not in scope of supply)
Operating current Max. 132 mA @ DC 24 V
Supervision contact Ohmic load:
Maximum switching voltage DC 30 V
Maximum switching current DC 1 A
Fibre optic cable Type of connection SC connector
Wavelength 1310 nm (for MM and SM)
Multi-mode
Range:
Fiber type 62.5/125 µm 13,100 ft
Fiber type 50/125 µm 6550 ft
Optical budget:
Fiber type 62.5/125 µm 11 dBm
Fiber type 50/125 µm 7.5 dBm
Single mode
Range:
Fiber type 9/125 µm 131,000 ft
Optical budget:
Fiber type 9/125 µm 29 dBm
Minimum optical attenuation
(corresponds to a minimum fiber length
of 13100 ft
3 dBm
FCnet/C-WEB Total length of line 3300 ft at 312 kbit/s
Impedance 120 Ω
Transmission mode Half-duplex
Cable type Shielded and unshielded cables

Questions and Answers: