EasyManua.ls Logo

Siemens FS20 - 5 Protective Zones

Siemens FS20
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Protective zones
5
14 | 42
Building Technologies
Fire Safety
2016
-
04
-
04
5 Protective zones
The protective zones are areas nested inside one another. Surge voltages are
reduced at the transition between protective zones.
Appropriate reduction measures:
External lightning measures
Room shielding and building shielding using steel reinforcement
Device shielding using metal housings
Use of suitable components on the connections
Protection is provided from the outside working in using protective zones.
Protective zone 0, outside (also protective zones 0/A, 0/B, 0/C, or 0/E)
Protective zone 1 within protective zone 0
Protective zone 2 within protective zone 1
Protective zone n within protective zones n-1
Position of protective zones and components:
Protective zone 0 is in the building shell area.
The fire detection installation is in protective zone 2.
The fire detection installation components may be in protective zone 2…n.
The same protective zones may be linked if the connection also corresponds to
the requirements of this protective zone.
Figure 1: Diagram for protective zones around and in buildings
BMA Fire detection installation Zone 1 Protective zone 1
G Building Zone 2 Protective zone 2
Zone 0 Protective zone 0
Lightning protection
Measures counteracting the effects of lightning are considered lightning protection.
External lightning protection relates to components outside the building.
Internal lightning protection relates to components inside the building.
Zone 2
Zone 0
Zone 1

Other manuals for Siemens FS20

Related product manuals