Parameters/address space
4.3 Substitute value behavior
IM 155-6 PN ST interface module (6ES7155-6AU01-0BN0)
26 Manual, 04/2017, A5E03576904-AE
4.3
Substitute value behavior
The substitute value behavior in the ET 200SP distributed I/O system is executed by the IO
controller for each slot.
The respective output behaves according to its configured substitute value behavior:
Current-free/voltage-free
Output substitute value
Keep last value
The substitute value behavior is triggered in the following cases:
STOP controller
Controller failure (connection interrupted)
Firmware update
Reset to factory settings
Station stop, for example, due to:
Missing server module
Removing more than one I/O module at a time.
At least one I/O module installed on an incorrect BaseUnit
Deactivating the IO device
Note
Reducing a configuration
If you reduce the configuration of the ET
200SP distributed I/O system and download the
configuration to the CPU, the modules which are no longer configured but still present
retain their original substitute value behavior. This applies until the supply voltage is
switched off at the interface mod
ule.
The "current-free/voltage-free" behavior takes effect in the following cases:
Firmware update
Reset to factory settings
Configuration control: The IM has not received a valid control data record 196 yet.
Incorrectly configured module
Module with incorrect parameter assignment