Interrupts, diagnostics, error, and system messages
5.1 Status and error displays
IM 155-6 PN ST interface module (6ES7155-6AU01-0BN0)
Manual, 04/2017, A5E03576904-AE
29
RN/ER/MT LED on the interface module
Table 5- 1 RN/ER/MT status and error displays
Off
Off
Off
Missing or insufficient supply voltage
on interface module.
Check the supply voltage or turn in on
at the interface module. *
On
On
On
Test of LEDs during startup: The three
LEDs light up simultaneously for ap-
-
Flashes
Off
Off
Interface module is deactivated. Activate the interface module with the
configuration software or the user pro-
Interface module is not configured. Configure the interface module with the
ET 200SP is reset to factory settings.
Not rele-
vant
Not rele-
vant
ET 200SP is currently exchanging data
with the IO controller.
Not rele-
vant
Flashes
Not rele-
vant
Group errors and group error channels. Evaluate the diagnostics data and
The configured structure does not cor-
respond to the actual structure of the
ET 200SP .
Check the structure of the ET 200SP to
see whether a module is missing or
defective, or whether a non-configured
Invalid configuration states. See section Invalid configuration states
of the ET 200SP on PROFINET IO
Parameter error in the I/O module. Evaluate the display of the module
status in STEP 7 and eliminate the
error in the respective I/O module.
Not rele-
vant
Not rele-
vant
Maintenance See section Maintenance events
(Page 36)
Flashes
Flashes
Flashes
The "Node flash test" is run (the LEDs
LK1 and LK2 of the PROFINET inter-
-
Hardware or firmware defective (the
LEDs LK1 and LK2 of the PROFINET
interface do not flash).
Run a firmware update. If the error
persists, contact Siemens Industry
Online Support.
Replace the interface module.
* PWR LED on (on the interface module): Check the backplane bus for a short circuit.