EasyManua.ls Logo

Siemens IM 155-6 PN ST - Error Display Codes and Causes

Siemens IM 155-6 PN ST
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Interrupts, diagnostics, error, and system messages
5.1 Status and error displays
IM 155-6 PN ST interface module (6ES7155-6AU01-0BN0)
32 Manual, 04/2017, A5E03576904-AE
Error display
The following table shows the possible causes of error that can occur.
Table 5- 5 Error display
Error type
(MAINT)
Error location
(ERROR/MAINT)
Cause of error
Remedy
1 02 to 32* The number of pulled I/O modules is
displayed. The diagnostics data is gen-
erated starting with two pulled I/O mod-
ules.
Check the configuration
of the ET 200SP.
65*
Missing server module
Interruptions at the backplane bus
Short circuit of communication on
the backplane bus
* Slot
Note
A short circuit in the backplane bus supply or the bus connection supply is indicated by the
following LEDs:
PWR LED: On
RN-, ER and MT LED: Off