Interrupts, diagnostics, error, and system messages
5.3 Alarms
IM 155-6 PN ST interface module (6ES7155-6AU01-0BN0)
40 Manual, 04/2017, A5E03576904-AE
USI structure = W#16#0006
Table 5- 13 USI structure = W#16#0006
W#16#0006 Manufacturer-specific diagnostics if an I/O module is in-
stalled on an incorrect BaseUnit.
Result: Station stop
• The I/O modules fail → substitute value behavior
• The interface module continues to exchange data with
the IO controller.
2
Followed by the slot for the I/O module:
Followed by 2 reserved bytes:
USI structure = W#16#0007
Table 5- 14 USI structure = W#16#0007
W#16#0007 Manufacturer-specific diagnostics if operation is not possi-
ble with existing bus configuration
Result: Station stop
• The I/O modules fail → substitute value behavior
• The interface module continues to exchange data with
the IO controller
2
Followed by the slot for the I/O module:
If slot 0 is specified, check the width of the station configuration (maximum 1 m).
Followed by 2 reserved bytes: