10/73 
Building Technologies Division  Basic Documentation LME39…  CC1P7106en 
  1 Safety notes  03.02.2016 
 
Connection BC interface OCI410  
 
Connect the BC interface OCI410 without other extension with the USB interface at 
your PC, follow the example design below. 
 
ACS410
PC software
LME39...
OCI410
7106z181e/0708
RJ11
USB2.0
 
Figure 3: Connection BC interface OCI410 
 
Connection interface OCI400... 
 
  Put the interface OCI400... in the connector at lockout reset button of LME39... 
Interface diagnostics works only if the AGK20... lockout reset button extension is 
not fitted 
  Connect the interface OCI400... without other extension to the interface at your 
PC, follow the example design below 
 
LME39...
OCI400
7106z182e/0708
ACS410
PC software
RS232
 
Figure 4: Connection interface OCI400... 
 
1.6 Electrical connection of flame detectors 
 
It is important to achieve practically disturbance- and loss-free signal transmission: 
  Never run detector cables together with other cables 
– Line capacitance reduces the magnitude of the flame signal 
– Use a separate cable 
  Observe the permissible length of the detector cables (refer to Technical data) 
  The ionization probe and the ignition electrode are not protected against electric 
shock hazard 
  Locate the ignition electrode and the ionization probe such that the ignition spark 
cannot arc over to the ionization probe (risk of electrical overloads) and that it 
cannot adversely affect the supervision of ionization 
 Insulation resistance 
– Must be a minimum of 50 M between ionization probe and ground 
– Soiled detector holders reduce the insulation resistance, thus supporting  
  creepage currents 
  Earth the burner in compliance with the relevant regulations; earthing the boiler 
alone does not suffice