Building Technologies Division  Basic Documentation LME39…  CC1P7106en 
  4 Type summary (other types on request)  08.12.2017 
4 Type summary (other types on request)  
 
The product nos. given below applies to the LME39… without plug-in base and without flame detector. For ordering information on plug-in bases and other accessories, refer to 
Ordering.
 
 
Article no.  Type 
Times in seconds 
 
tw 
 
max.
s 
TSA 
 
max. 
s 
tfz 
(P228)
approx.
s 
t1 
(P225)
min.
s 
t1' 
(P256) 
min. 
s 
t3 
(P226)
approx.
s 
t3n 
(P257) 
approx. 
s 
t4 
(P230)
approx.
s 
t8 
(P234)
min.
s 
t10 
(P224)
approx.
s 
t11
(P259)
min.
s 
1)
 
t12 
(P260) 
min. 
s 
1)
 
t22 
(P231) 
max. 
s 
BPZ:LME39.100C1 LME39.100C1 
Requirement 2.5  3  0.3  30  ---  3  2.5  10  0  180  30  30  --- 
BPZ:LME39.100C2 LME39.100C2 
Requirement 2.5  3  0.3  30  ---  3  2.5  10  0  180  30  30  --- 
Setting range 
Min. ---  0.3  0  0  ---  1.2  0 + 0.3  1.2  0  0  0  0  --- 
Max. ---  37.5 + 1.5 + 0.3 1.5  75  ---  37.5  37.5 + 0.3 75  1237 179.5  75  75  --- 
Increments (s) ---  0.147  0.147  0.294 ---  0.147 0.147  0.294 4.851 4.851  0.294 0.294  --- 
Factory setting ---  t3n + tfz  0.294  32.34 ---  3.234 2.205 + 0.3 9.996 0  179.487 32.34 32.34  --- 
 
BPZ:LME39.400C1 LME39.400C1 
Requirement 2.5  5  0.3  ---  14.5  1.7  4.4  10  0  ---  ---  ---  5 
BPZ:LME39.400C2 LME39.400C2 
Requirement 2.5  5  0.3  ---  14.5  1.7  4.4  10  0  ---  ---  ---  5 
Setting range 
Min. ---  0.3  0  ---  0  1.2  0  1  0  ---  ---  ---  0 
Max. ---  37.5 + 1.5 + 0.3 1.5  ---  75  37.5 37.5 + 0.3  75  1237  ---  ---  ---  7.4 
Increments (s) ---  0.147  0.147 ---  0.294  0.147 0.147  0.294 4.851 ---  ---  ---  0.147 
Factory setting ---  t3n + tfz  0.294 ---  15.582  1.911 4.116 + 0.3  9.996 0  ---  ---  ---  4.557 
 
Function parameter  Parameter number  Factory setting 
Repetition limit value loss of flame and no flame at the end of safety time 
0 = none 
1 = none 
2 = 1 x repetition 
3 = 2 x repetition 
4 = 3 x repetition 
240  1