22/73
Building Technologies Division Basic Documentation LME39… CC1P7106en
6 Technical data 08.12.2017
6 Technical data
6.1 General unit data
Mains voltage
- LME39.xxxx1
- LME39.xxxx2
AC 120 V
AC 230 V
Mains frequency 50...60 Hz
Power consumption 12 VA
External primary fuse (Si) Max. T10H250V to IEC 60127-2
Recommendation:
T6.3H250V to IEC 60127-2
Mounting position Optional
Input current at terminal 12 Max. 5 A
Weight Approx. 160 g
Safety class I
(burner control with plug-in base)
In accordance with DIN EN 60730-1
For applications without safe separation.
Protection against electric shock is
achieved through double or reinforced
insulation. Provision for the protective
earth connection is made in the plug-in
base AGK11.
Degree of protection IP40 (to be ensured through mounting)
(if RJ11 jack is not covered, only IP10)
Rated surge voltage
category III (DIN EN 60664)
LME39 total unit 4 kV
Creepage distances and air gaps 2.5 kV due to voltage limitation measures
Pollution degree 2 in accordance with DIN EN 60730-1
Software class Class C in accordance with
DIN EN 60730-2-5:2011
2-channel structure
Reaction time in the event of loss of flame Max. 1 s
Perm. cable length terminal 1 Max. 1 m at a line capacitance of 100
pF/m, unshielded
(max. 3 m at 15 pF/m)
Perm. cable length from QRA… to
AGQ3.xA27 (lay separate cable)
Max. 20 m at 100 pF/m, unshielded
Perm. cable length terminals 8, 10 and 11 Max. 20 m at 100 pF/m, unshielded
(lay separate cable)
Perm. cable lengths other terminals Max. 3 m at 100 pF/m, unshielded
Perm. input voltage terminals 6 and 11 AC 120 V
AC 230 V
Possible input current terminal 6 0.5 mA
Possible input current terminals 8 and 11 1 mA
Perm. terminal rating At cos 0.6 At cos = 1
- Terminal 3 Max. 2.7 A (15 A for max. 0.5 s) Max. 3 A
- Terminals 4, 5 and 7 Max. 1.7 A Max. 2 A
- Terminal 9
- LME39.100... Max. 1 A Max. 1 A
- LME39.400... Max. 1,7 A Max. 2 A
- Terminal 10 Max. 1 A Max. 1 A
Table 2: Perm. terminal rating