Building Technologies Basic Documentation LME7... CC1P7105en
13 Operation via AZL2 17.04.2018
13.6.2.4. Number of startups resettable
Β
Note!
Can be deleted for service (see chapter Parameter list)!
P
V
h
min
s%
Bild34/0707
On the left, parameter 164: is displayed blinking.
On the right, characters ._._ appear.
Example: Parameter 164: ._._
/reset
1…3 s
P
V
h
min
s
%
Bild 201/1008
Pressing the
/reset
button (13 seconds) and
releasing it when ._._ flashes displays the number
of startups (can be reset).
Example: 000036
/reset
3…8 s
P
Vhmins%
Biod73/0707
Press
/reset
for 3…8 seconds to go to the range
that can be changed.
Digit 0 blinks.
/reset
P
V
hmins%
Bild163/1107
By pressing
/reset
, the number of startups is reset
to 0.
Display: 000000
/reset
or
ESC
P
V
h
min
s%
Bild34/0707
Press
/reset
or
ESC
to show parameter 164
blinking again.
To the next parameter
Back to the previous
parameter