EasyManua.ls Logo

Siemens LME73 - Fault status messages and error display

Siemens LME73
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
92/106
Building Technologies Basic Documentation LME7... CC1P7105en
15 Operation via internal LED 17.04.2018
15.4 Fault status messages, display of errors
15.4.1 Display of errors (faults) with lockout
LCD Bild 06/0908
Alternately
LCD Bild 07/0908
Display shows alternately Loc and 4.
Unit is in the lockout position.
The current error code is displayed and the signal lamp is
blinking red.
Example: Error code 4
+
or
-
LCD Bild 08/0908
Press
+
or
-
for display of the phase, where the fault
appeared.
Signal lamp blinks red.
Example: Phase P02
A
Only with modulation via analog signal
Press
A
for display of the output position / actuator
position where the error occurred.
Signal lamp lights up red.
Example: Output position / actuator position 49

Table of Contents

Other manuals for Siemens LME73

Related product manuals