Siemens Building Technologies Basic Documentation LMU54... / LMU64... CC1P7494en
HVAC Products 3 Functions 07.11.2002
Like the first stage plus limitation of the minimum volumetric flow to ensure the
measured T will not exceed the adjusted Tmax (dTkTrMax)
Control of Tmax via the volumetric flow.
20 15 10 5 0 -5 -10 -15 -20
20
30
40
50
60
70
80
90
100
Temperature [°C]
20 10 0 -10 -20
Acquired return
temperature
0
100
Modgrad [%]
NqmodNenn
(= 18)
corresponding to 100 %
TiAussenNorm
(= -20)
Range in which the delta-T controller
adjusts the volumetric flow
TkSNorm
(= 70)
7494d36E/0102
NqmodMin
(= 40)
dTkTrNenn
(= 20)
dTkTrMax
(= 30)
Required flow temperature
Required flow temperature
at NqmodNenn
Outside temperature [°C]
Outside temperature [°C]
Theoretical return
temperature at NqmodNenn
Range of reduced volumetric flow
(= NqmodMin)
T supervision
Condensing boilers with return temperature sensor to increase the efficiency of
condensation and when there are limitations with regard to the heat exchanger’s
maximum T.
No bypass allowed.
As before, the pump is activated and deactivated via the AC 230 V line. The pump’s
speed is adjusted via a separate control line
The pump is controlled by means of a pulse width-modulated DC signal (PWM =
Pulse Width Modulation)
Automatic maximum operation should the control line become faulty
FoerderMax
(= 5.9)
FoerderMin
(= 0.6)
Speed = 1
6
5
4
3
2
1
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
7494d37E/0102
Speed = QmodDrehzStufen
Pump head [m]
Q [m
3
/ H]
H-Q chart of PWM pump
Third stage
T supervision
Application
PWM pump control
H-Q chart
(example)