118/301 
Siemens Building Technologies  Basic Documentation LMV5...  CC1P7550en 
HVAC Products  7 Display and operating unit AZL5...  13.08.2004 
 
2) End of a successful adaption 
After the adaption, the relevant characteristics will be displayed. 
 
By pressing the 
Selection buttons, the P-, I- and D-parts as well as the acquired loop 
delay time Tu will be displayed: 
 
A d a p t i o n  o k  
P - P a r t  ( X p )   
 X 2 5 . 0 % 
C o n t i n u e  w i t h  < > 
 
A d a p t i o n  o k  
I - P a r t  ( T n )  
 4 0 0 s 
C o n t i n u e  w i t h  < > 
 
A d a p t i o n  o k  
D - P a r t  ( T v )  
 3 5 s 
C o n t i n u e  w i t h  < > 
 
A d a p t i o n  o k  
D e l a y   T i m e    ( T u )   
 1 0 s 
C o n t i n u e  w i t h  < > 
 
3) Canceling the adaption 
If the LC was not able to select a suitable loop, it will stop the adaption and display the 
following text. 
 
If a running adaption is manually canceled by pressing 
Esc, the following text will also 
appear: 
 
A d a p t i o n  
c a n c e l e d   
   
C o n  t  i  n u e    w    E S C     
 
The system changes to «Normal operation». In that case, the previous PID parameters 
will be maintained.