77/301 
Siemens Building Technologies  Basic Documentation LMV5...  CC1P7550en 
HVAC Products  6 Temperature or pressure controller (internal load controller LC)  13.08.2004 
 
 
Optimum adaption of the controllers to the controlled system can be checked by re-
cording the actual value during startup while the controlled system is working. The dia-
grams below reveal incorrect settings and give hints on remedy. 
 
Here, the behavior of a controlled system of the 3
rd
 order for a PID controller is shown. 
The procedure for setting the control parameters can also be applied to other types of 
controlled systems. 
Practical value for «TN : TV» = 4...6. 
 
XP too small  XP too great 
t
x
w
7550d21/0501
 
t
x
w
7550d22/0501
 
 
 
Tn and Tv too small  Tn and Tv too great 
t
x
w
7550d23/0501
 
t
x
w
7550d24/0501
 
 
 
Optimum setting 
t
x
w
7550d25/0501
 
 
Checking the control 
parameters 
Example