The burner travels to the ignition load. The burner’s output should now be increased 
manually and in steps of the curve setting until the nominal capacity (100 %) is 
reached. During the manual procedure, the actuators travel on the interpolated straight 
line to the maximum position of 90° at 100 % output. The flue gas values and the stabil-
ity of the flame must be constantly checked. It may be necessary to define provisional 
curvepoints, which can be canceled again later. As soon as the nominal capacity is 
reached, the burner should be optimized with regard to flue gas values. 
 
It is recommended to measure the gas throughput at 
each curvepoint in order to reflect 
the real burner output on the display in relation to the maximum gas throughput. 
 
• Press the 
ESC button to leave the curvepoint setting 
•  Store the point by pressing 
Enter 
•  Now, select the second curvepoint. The settings of the previous curvepoint will be 
adopted on a preliminary basis 
•  Store the second curvepoint like the first one 
 
During storage, the LMV5... sorts the curvepoints based on rising output. This means 
that you can enter the curvepoints in any order you like as long as the output was cor-
rectly set. Proceed in this way point by point until the minimum output is reached. After 
storage of the minimum output point, leave the curve setting. 
 
Menu level 1  Menu level 2  Menu level 3  Menu level 4  Menu level 5  Menu level 6 
Params & Display           
 
RatioControl 
       
 
  GasSettings 
     
     
CurveParams 
   
       
Point 
 
       
Manual 
 
 
Example: 
 
Point  1  2  3  4  5 
Order of setting  5  4  3  2  1 
Output  15 %  28 %  50 %  71 %  100 % 
Gas  8.6°  28.0°  43.0°  62.5°  81.5° 
Air  10.5°  28.8°  46.0°  55.7°  70.8° 
Aux  20.3°  30.0°  45.0°  52.0°  60.0° 
 
90
80
70
60
50
40
30
20
10
0
0 102030405060708090100 %
Fuel / air ratio control
Load [%]
Position [°]
Gas actuator position
Air actuator position
Auxiliary actuator
7550d26E/0502
 
 
15. Setting the curve 
First setting 
Note