Error 
code 
Diagnostic 
code 
Device  Display  Meaning for the LMV5x system  Troubleshooting 
C5 04 
 
ABE  Version Conflict  Software of the AZL5... too old  Replace AZL5... or update its software 
C5  08  SA  Version Conflict  Software of 1 or several actuators too old  Replace actuator 
C5 10 VSD module
Version Conflict  Software of VSD module too old  Replace basic unit 
C5  20  O2  Version Conflict  Software of O2 module too old  Replace O2 module 
D1  #  VSD module  Fault Feedback VSD Module  Basic unit has detected a wrong state of 
the VSD module. Corresponds to the "8x"-
faults with the other CAN users 
If fault occurs sporadically: Improve EMC. 
If fault occurs constantly: Replace defective module 
D1  01 
 
VSD module
Fault Feedback VSD Module  CRC error   
D1  02 
 
VSD module
Fault Feedback VSD Module  Key error main loop counter   
D1  03 
 
VSD module
Fault Feedback VSD Module  No feedback for max. number   
D3  #  O2  Fault Feedback O2 Module  Basic unit has detected a wrong stage of 
the O2 module 
Check CAN cabling and terminators as specified 
If fault occurs sporadically: Improve EMC 
If fault occurs constantly: Replace defective module 
D3  01 
 
O2  Fault Feedback O2 Module  CRC error   
D3  02 
 
O2  Fault Feedback O2 Module  Key error main loop counter   
D3  03 
 
O2  Fault Feedback O2 Module  No feedback for max. number   
E1  ---  VSD module  Fault Feedback VSD Module  Basic unit has detected a ROM-CRC fault 
in the VSD module when checking its 
feedback signal 
If fault occurs sporadically: Improve EMC 
If fault occurs constantly: Replace defective module