Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 18 Addendum 3: Variable speed drive (VSD) module 13.08.2004
18.2 Differences to LMV51.200... and LMV51.000... /
LMV51.100
6.3.1 Menu structure
Selection of 1) will take you to:
Selection menu «GasSettings»
Only the data associated with the currently active type of fuel can be parameterized.
S p e c i a l P o s i t i o n s
1)
C u r v e P a r a m
2)
L o a d L i m i t s
3)
A u x A c t u a t o r
4)
Selection of 1) (Home Pos, Prepurge Pos...), 3) and 4) will take you to the standard
parameterizations of the specified parameters.
Selection of 4) will take you to:
Standard parameterization «Auxiliary Actuator»
Here, the function of the auxiliary actuator can be separately selected for each type of
fuel: deactivated / activeDamper / VSD active.
A u x A c t u a t o r
C u r r : d e a c t i v a t e d
N e w : V S D a c t i v a t
With «VSD active», the VSD takes the place of the auxiliary actuator (menus «Aux Ac-
tuator», «Auxiliary»). The available setting values reach from 0 to 100 %.
6.3.2 Changes when setting ratio control via manual control
The system extrapolates the VSD to a minimum speed of
10 % and a maximum speed
of 100 %.
100 %
90°
7550d07e/0704
Pos.
Load
0 %
AUX
FUEL
AIR
Ignition = low fire
Change of load / position resulting from an automatically entered point
Special functions
Curve settings for
electronic ratio control