EasyManuals Logo

Siemens MIDIMASTER Vector User Manual

Siemens MIDIMASTER Vector
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
English 6. SYSTEM PARAMETERS
Parameter Function Range
[Default]
Description / Notes
G85139-H1751-U529-D1 © Siemens plc 199
9
4/8/99
46
P023 ·
Analogue input 1 type 0 - 3
[0]
Sets analogue input type for analogue input 1, in conjunction with the settings
of the DIP selector switches 1, 2 and 3 (see Figure 4.1.2). :
0 = 0 V to 10 V/ 0 to 20 mA Unipolar input
1 = 2 V to 10 V/ 4 to 20 mA Unipolar input
2 = 2 V to 10 V/ 4 to 20 mA Unipolar input with controlled start /
stop when using analogue input control.
3 = -10V to +10V Bipolar input. -10V corresponds to left rotation at speed
set in P021, +10V corresponds to right rotation at speed set in P022
Note: Setting P023 = 2 will not work unless the inverter is under full local
control (i.e. P910 = 0 or 4) and V ³ 1 V or 2mA.
WARNING: The inverter will automatically start when voltage goes
above 1V. This equally applies to both analogue and digital
control (i.e. P006 = 0 or 1)
Bi-polar Input Operation
P024 ·
Analogue setpoint addition 0 - 2
[0]
If the inverter is not in analogue mode (P006 = 0 or 2), setting this parameter
to:
0 = No addition to basic setpoint frequency as defined in P006.
1 = Addition of analogue input 1 to the basic setpoint frequency as
defined in P006
2 = Scaling of basic setpoint (P006) by analogue input 1 in the range
0 -100%.
P025 ·
Analogue output 1 0 - 105
[0]
This provides a method of scaling the analogue output 1 in accordance with
the following table:
Use range 0 - 5 if minimum output value = 0 mA.
Use range 100 - 105 if minimum output value = 4 mA
P025 =
Selection
Analogue Output Range Limits
0/4 mA 20 mA
0/100
Output frequency 0 Hz Output frequency (P013)
1/101
Frequency
setpoint
0 Hz Frequency setpoint (P013)
2/102
Motor current 0 A Max. overload current
(P083 x P086 / 100)
3/103
DC-link voltage 0 V 1023 Vdc
4/104
Motor torque -250% +250%
(100% = P085 x 9.55 / P082 Nm)
5/105
Motor RPM 0 Nominal motor RPM (P082)
6/106
Motor
magnetising
current
0 A Max. overload current
(P083 x P186 / 100)
7/107
Motor torque
producing
current
(centre zero)
0 A
Max
regenerative
torque
Max. overload current
i.e. accelerating torque
(P083 x P186 / 100)
F max
F min
+10V
0.2V Hysteresis
-10V
P021
P022

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MIDIMASTER Vector and is the answer not in the manual?

Siemens MIDIMASTER Vector Specifications

General IconGeneral
BrandSiemens
ModelMIDIMASTER Vector
CategoryMedia Converter
LanguageEnglish

Related product manuals