7ML19985DG02 Milltronics MillPulse 600 – INSTRUCTION MANUAL Page 3
Specifications
Switching Capability
voltage: 18 to 48 V AC/DC +/-10%, 50/60 Hz (Jumper In)
60 to 135 V AC/DC +/-10%, 50/60 Hz (Jumper Out)
current 5 to 400 mA continuous
2 A surge for 20 msec at 1 operation per second
Voltage Drop
•8 V
Residual Current
•1.5 mA
Fuse
1A, 250 V, SLO-BLO, 4.5 x 14.5 mm (not operator replaceable)
Switch Duration
on: 50 msec minimum
off: 50 msec minimum
Operating Limit
600 pulses per minute maximum
Operating Temperature
-45 to 60 °C (-45 to 140 °F)
Display
red LED for switch status
Construction
probe body: aluminum
process mounting: 2” NPSL
connection box: aluminum
3/4” NPT conduit entrance
4 screw terminals for maximum 12 AWG wire size
gasketing: neoprene