MJ-5 Communications Module
19
No Analog Outputs in the Simple set currently.
6.2.6 Metering
Binary Inputs
LOW Voltage Limiting, [1=On]
HIGH Voltage Limiting, [1=On]
Automatic Operation, [1=Inhibited]
Power Flow Direction, [0=Fwd, 1=Rev]
R/A/M Switch, [0=Off/Manual, 1=Auto/Remote]
Voltage Reduction Input 1, [0=Open, 1=Closed]
Voltage Reduction Input 2, [0=Open, 1=Closed]
Supervisory Switch, [0=Off, 1=On (Remote)]
Neutral Position Status, [0=inactive, 1=active]
Low Battery Status, [0=inactive, 1=active]
Raise Limit Reached, [0=inactive, 1=active]
Lower Limit Reached, [0=inactive, 1=active]
Binary Outputs
Remote Auto/Manual (1=block)
Fwd Voltage Level (+/-.1V) (0=dec, 1=inc)
Bandwidth Voltage (+/-.1V) (0=dec, 1=inc)
Fwd Time Delay (+/- 5s) (0=dec, 1=inc)
Fwd Reactive Comp (+/- 1V) (0=dec, 1=inc)
Local Voltage Reduct (1=Active)
Remote Volt Reduct (1=Active)
Local Volt Reduct % (+/-.5V) (0=dec, 1=inc)
Remote Volt Red. % (+/-.5V) (0=dec, 1=inc)
Fwd Resistive Comp (+/- 1V) (0=dec, 1=inc)
Reset Demands & min/max (AI 20-26)
Reset Energies (AI 27-28)
Analog Inputs
Operations Counter (100's)
Operations Counter (10's and 1's)
Hardware Status (0=All Good)
Primary Load Current in Amps
Compensated Voltage (Sec.)
% Voltage Reduction in Effect