4 Setting Up the MJ-5 Control Panel 
Siemens Industry, Inc.     36 
  MAC: This item will display MAC address of the 
network. 
  InitDataPort:  This item it used to reinitialize the 
front data port in case of loss of communication.  
If panel is not communicating to MJXplorer or 
DNP Config tool, then the user can press 
change/save key and select yes.  This will 
reinitialize the data port.   
  U: This item is for Diagnostic purposes to check 
if calibration is done. 
  P: This item is for Diagnostic purposes to check 
if calibration is done. 
  C: This item is for Diagnostic purposes to check 
if calibration is done. 
The <DIAGNOSTICS> menu also includes the Serial 
Number and Product Revision code for the MJ-5 Control 
Panel. These are set at the factory and cannot be changed. 
 
The configurable tap changer control settings are also 
contained in the <DIAGNOSTICS> menu. Contact your 
Siemens representative for more information before 
adjusting these settings. 
 
 
4.10 Setting up the Quick Key 
The Quick Key provides access to the customizable Quick 
List. The Quick List can be used to step through a series of 
up to 15 user-set menu items. The Quick List allows 
creation of a custom menu with the minimal amount of 
effort. Any changes to the menu parameters must be done 
using normal configuration and operation procedures. 
Certain menus cannot be added to the Quick List including: 
Password menu, Log menu(s), Alert menu. Press the Quick 
Key repeatedly to step through the Quick List. 
 
Adding Items to the Quick List:  
Use the scroll keys to display the desired menu item to be 
added. Press and hold the Quick key for 3 seconds. The 
phrase “Quick Added” will appear indicating that the data 
item has been added. 
 
Removing Items from the Quick List:  
Press the Quick Key repeatedly to display the menu item to 
be removed. Once the desired item is selected, hold the 
Min/Max key for 3 seconds. The phrase “Quick Delete” 
will appear on the display.