7.3 RS-232 Connections
The following section describes the connection requirements for RS-232 cable. This cable will allow you to connect
the MJ-X
L
Control Panel to an RTU or personal computer.
Five of the standard RS-232 wires are used for this application.
Signal Return (RTN)
RXD
TXD
CTS
RTS
Table 7-2 lists the connections that must be made to connect the MJ-X
L
RS232/485 Communications Module to a
personal computer, RTU, or other supervisory device. The MJ-X
L
Communications Module defaults to
no-handshaking-required mode. However, the communications module asserts RTS while it transmits data, but the
module will ignore the CTS input signal.
Table 7-2 RS-232 Intelligent Electronic Device Wiring
MJ-X
L
RS-232/485
Communications Module
Personal computer, supervisory
device, or other network device
RTN Signal Ground
RXD TXD
TXD RXD
Table 7-3 lists the connections that must be made to connect the MJ-X
L
RS232/485 Communications Module to a
modem.
Table 7-3 Modem Wiring
MJ-X
L
RS-232/485
Communications Module
Modem
RTN Signal Return
RXD RXD
TXD TXD
RTS RTS
CTS CTS
RXDis an input for Data Terminal Equipment (DTE) and an output for Data Communications Equipment
(DCE). TXDis an output for the DTE and an input for the DCE. Personal computer serial ports are configured
as DTE and the modems are configured as DCE. The communications module RS-232 connections implement
DTE.