Connectable components
9.3 PP 72/48D 2/2A PN
NCU 7x0.3 PN
Manual, 09/2011, 6FC5397-1EP40-0BA0
133
Table 9- 48 Technical specifications in the "voltage input" operating mode
Parameter Value
Input range (rated value) - 10 V to + 10 V
permitted overrange - 11.75 V to + 11.75 V
Resolution 16 bits (including sign)
Accuracy +/- 0,5 %
Internal resistance Ri 100 KOhm
Table 9- 49 Technical specifications in the "current input" operating mode
Parameter Value
Input range (rated value) - 20 mA to + 20 mA
Permitted overrange - 23.5 mA to + 23.5 mA
Resolution 16 bits (including sign)
Accuracy +/- 0,5 %
Internal resistance Ri 133 ohm
Table 9- 50 Technical data in the "PT100" operating mode
Parameter Value
Input range (rated value) - 200 ℃ to + 259 ℃
Standard EN60751
Resolution 16 bits (including sign)
Accuracy +/- 2 ℃
Internal resistance Ri >> 10 kOhm
CAUTION
If the PT100 operating mode is selected, the hardware is protected against overvoltage.
In the event of an error the following occurs:
1. An error bit is set which is then communicated to the PLC.
2. The module is shut down.
Measurement using a 4-wire connection system
Notes regarding the connection and operation of PT100 resistors:
This enables the module to supply X3 with a constant current via the CO1, CI1, CO2 and CI2
terminals. The constant current is fed to the resistor to be measured where it is then
measured as the voltage drop. It is imperative to wire the connected constant current cables
directly to the resistor.