Connectable components
9.1 NX10.3 / NX15.3
NCU 7x0.3 PN
Manual, 09/2011, 6FC5397-1EP40-0BA0
89
DRIVE-CLiQ interfaces X100 - X103
Table 9- 4 Characteristics of X100 - X103
Characteristic Version
Connector type DRIVE-CLiQ plug
DRIVE-CLiQ standard (inside the control cabinet) Cable type
MOTION CONNECT (outside the control cabinet)
Max. cable length 70 m
Table 9- 5 Pin assignment, X100 - X103
Pin Signal name Technical specifications
1 TXP Transmit data +
2 TXN Transmit data -
3 RXP Receive data +
4 - Reserved, do not use
5 - Reserved, do not use
6 RXN Receive data -
7 - Reserved, do not use
8 - Reserved, do not use
A + (24 V) Power supply
B M (0 V) Ground
DRIVE-CLiQ topology
NX components can be connected to the Control Unit via DRIVE-CLiQ. The following rules
apply for the wiring:
Only one star topology is permitted between the NX and the Control Unit. This means
that only one NX can be operated per DRIVE-CLiQ port on a Control Unit.
DRIVE-CLiQ ports not assigned to NX can be wired to other DRIVE-CLiQ components.
Once an NX has been connected and configured, you cannot simply insert it into a
different DRIVE-CLiQ port, as the addresses of the integrated drives are set permanently
from the point of view of the PLC. The following table illustrates this relation:
Table 9- 6 NX PROFIBUS addresses
DRIVE-CLiQ port on the NCU Drive PROFIBUS addresses
X105 15
X104 14
X103 13
X102 12
X101 11