EasyManua.ls Logo

Siemens OOH740-A9-Ex - Specification

Siemens OOH740-A9-Ex
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Planning
4
Parameter sets for addressed operation
39
Building Technologies A6V10367521_h_en_--
Fire Safety 2015-02-02
4.3.2.2 Specification
No. Name Operating temperature
typ. / max.
Static activation
temperature
1
Differential activation
temperature
2
Differential activation
possible from:
[°C] [°C] T [K] [°C]
1 A1R
60 °C rate of rise
25 / 50 60 25 3
2 BR
80 °C rate of rise
40 / 65 80 29 30
3 A1S
60 °C maximum
25 / 50 60
4 BS
80 Maximum
40 / 65 80
14 Application-specific parameter sets
15
1
Applicable with slow temperature increases <1 K/min.
2
Applicable with fast temperature increases of >10 K/min. When there is a slow
temperature increase of <10 K/min, this value rises by a few degrees.
All parameter sets apart from 14 and 15 comply with standard EN