Mounting/Installation
5
Technical Ambient Supervision Message
45
Building Technologies A6V10367521_h_en_--
Fire Safety 2015-02-02
5 Mounting/Installation
WARNING
Electrostatic charging when installing devices in an area at risk of explosion
Risk of explosion
Only install devices if the atmosphere in the mounting area is not at risk of
explosion.
Observe the relevant regulations and recommendations for installing devices
in areas at risk of explosion.
Peripheral devices approved in accordance with D
irective 94/9/EC (ATEX
directive) may only be commissioned on a test basis in such a way that internal
components required for explosion protection are not damaged in a way that goes
unnoticed. Therefore, it is only permitted to operate C-NET-Ex peripheral devices
in conjunction with a line adapter (Ex) FDCL221-Ex.
It is only permitted to operate peripheral devices on a collective detector line in a
potentially explosive atmosphere with a safety barrier SB2 or SB3.