Mounting/Installation
5
Connecting the detector base
57
Building Technologies A6V10367521_h_en_--
Fire Safety 2015-02-02
5.10.3 Connection diagram (collective)
WARNING
Connecting cables in environments at risk of explosion
Risk of explosion
Only connect cables in an environment that is not at risk of explosion.
The following applies to collective detector lines:
l The detector line must start with a safety barrier SB2 or SB3.
l Connect a control panel-specific end-of-line (EOL) to the end of the collective
detector line.
l External alarm indicators may only be connected to one detector.
l Only use external alarm indicators FDAI9x-Ex.
The connection is established from base to base using twisted or non-twisted wire
pairs.
+
-
+
-
+
-
+
-
+
-
+
-
LINE
+
-
+
-
+
-
SB2
SB3
+
-
+
-
LINE
+
-
2
3
1
4
R
5
Connection diagram for collective detector line with and without external alarm indicator
1
Control panel
4
End
-
of
-
line depending on control panel
2
Detector base FDB201, FDB202
5
Parameter set resistor R
3
External alarm in
dicator FDAI9x
-
Ex