Commissioning
Fault detection, correction or reset
2
14
| 22
Siemens
Building Technologies
2.2 Fault detection, correction or reset
Detect and correct faults
The status LED blinking red indicates a failure or wrong configuration
Read out Error Code (register 4x0002) value 0…11 (see table below)
Further information contain
Status register of pressure sensor
Status register of universal inputs
Value
Error code (register
4x0002)
Reliability pressure
sensor (register 4x0004
+ 4x0006)
Reliability analog
inputs (register
4x0008 + 4x0010)
0 no error no error no error
1 no sensor disruption in operation sensor not
connected
2 overload overload temperature >
150ºC
3 underload negative pressure temperature < -
50ºC
4 open loop
5 short time overload short time overload
6 no output signal
7 other error zero point reset required
8 calculation error
9 extended error
10 EEPROM
protection active
11 configuration error configuration error configuration error
Reset to factory setting
Use the push button to do a reset to factory setting. The Sensor is reset to
delivered setting. Factory settings are listed in the register list "Modbus registers
[➙ 16]" default values.
Hold the push button for 20…30 seconds.