Siemens RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation CE1P3182en
Building Technologies Functions 28 May 2009
4.12.1 Parameters Service level
Parameter
Name Factory setting Range
RDG400
Service level
P01 Control sequence When 2-pipe /
2-stage:
1 = Cooling only
When 4-pipe:
4 = H and C
0 = Heating only
1 = Cooling only
2 = H/C changeover manual
3 = H/C changeover auto
4 = Heating and Cooling
P02 User operating mode profile (mode button) 1 1 = (Auto) - Comfort - Protection
2 = (Auto) - Comfort - E Saving - Prot
P04 Selection of °C or °F 0 (°C) 0 = Degrees Celsius (°C)
1 = Degrees Fahrenheit (°F)
P05 Sensor calibration (intern, extern) 0 K – 3 ... 3 K
P06 Standard temperature display 0 0 = Room Temperature
1 = Setpoint
P07 Display info line
(2nd line of LCD)
0 0 = --- (No display)
1 = °C and °F
0..1
P08 Comfort setpoint 21 °C 5 ... 40 °C
P09 Minimum setpoint in Comfort mode 5 °C 5 ... 40 °C
P10 Maximum setpoint in Comfort mode 35 °C 5 ... 40 °C
P11 Energy Saving heating setpoint 15 °C OFF, 5 ... WcoolE-saving;
(WcoolE-saving = 40 °C max)
P12 Energy Saving cooling setpoint 30 °C OFF, WHeatE-saving ... 40 °C;
(WHeatE-saving = 5 °C min)
P14 Button lock function 0 0 = Unlocked
1 = Auto locked
2 = Manual locked
Parameter display depends on selected application and function