8/49 2015-02-27 CE1G2201xx
3 Function check
a) Check the display. If there is no display, check the batteries
b) “Continuously Comfort mode“ , read the temperature
displayed
c) Set the temperature setpoint to a level above the displayed
room temperature (see operating instructions)
d) The relay and thus the actuating device must respond within 1
minute. Symbol ▲ appears on the display. If not:
· Check actuating device and wiring
· The room temperature is possibly higher than the adjusted
temperature setpoint
e) Set temperature setpoint of “Continuously Comfort mode“
to
the required level
f) Select the required operating mode
4 Reset
User-defined settings:
Press simultaneously
, and for 3 seconds:
All temperature and time settings of the slider positions are reset to
their default values (refer to section “Factory settings“ in the
operating instructions). The settings made on the expert level will
remain unchanged.
The clock starts at 12:00, the date on 01-01-08
(01 – January - 2008). During the reset time, all sectors of the
display are illuminated and can thus be checked.
All user-defined settings plus those made on the expert level:
Press simultaneously the DIP switch reset button,
and
for 5 seconds:
After this reset, all factory settings will be reloaded. This applies
to both the slider settings and the settings made on the expert level.
Notes
· The controller is classified as a device of software class A and
designed for use in environments with normal degree of
pollution