MaxVIMMXU*.TotVAr
Information Value
Reactive Power (Q =) MaxVIMMXU*.TotVAr.instmag.f Measured Value Value
MaxVIMMXU*.TotVAr.mag.f Measured Value Value
MaxVIMMXU*.TotVAr.units.SIunit 63 VAr
MaxVIMMXU*.TotVAr.units.multiplier 0 1
MaxVIMMXU*.TotW
Information Value
Active Power (P =) MaxVIMMXU*.TotW.instmag.f Measured Value Value
MaxVIMMXU*.TotW.mag.f Measured Value Value
MaxVIMMXU*.TotW.units.SIunit 62 W (Watt)
MaxVIMMXU*.TotW.units.multiplier 0 1
MinMMXU*.Mod
Information
Reset Device x
MinMMXU*.Mod.stVal 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
MinMMXU*.Health
Information
Device Healthy 0 1
MinMMXU*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
Device Functionality
3.6 Data Storage
Reyrolle 7SR5, Transformer Protection Device, Device Manual 107
C53000-G7040-C015-1, Edition 11.2019