Functions > Protection > 50G > Gn 50G-n
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
81HB2 Inhibit No
Yes
No
79 Delayed Inhibit No
Yes
No
IEC 61850 Functional Information Mapping
A50GPTOC*.Mod
Information
50G Earth Fault Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A50GPTOC*.Mod.stVal 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A50GPTOC*.Health
Information
Device Healthy 0 1
A50GPTOC*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A50GPTOC*.Op
Information
Element Operated 0 1
A50GPTOC*.Op.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
5.12.6
Protection and Automation Functions
5.12 50G Instantaneous Earth Fault – Measured
Reyrolle 7SR5, Transformer Protection Device, Device Manual 219
C53000-G7040-C015-1, Edition 11.2019