Scheme 2 (Intermediate)
[dw_7SR5_function74TCSettingExample2, 1, en_US]
Figure 6-13 Trip‑Circuit Supervision Scheme 2 (H6)
Scheme 2 provides continuous trip‑circuit supervision of the trip coil with the circuit‑breaker Open or Closed.
It does not provide pre-closing supervision of the connections and links between the tripping contacts and the
circuit‑breaker and may not therefore be suitable for some circuits which include an isolating link.
Scheme 3 (Comprehensive)
[dw_7SR5_function74TCSettingExample3, 1, en_US]
Figure 6-14 Trip‑Circuit Supervision Scheme 3 (H7)
Scheme 3 provides full trip supervision with the circuit‑breaker Open or Closed.
Settings Menu
Functions > Function Config
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
74TC Trip‑Circuit Enabled
Disabled
Disabled
6.5.5
Supervision Functions
6.5 74TC Trip-Circuit Supervision
Reyrolle 7SR5, Transformer Protection Device, Device Manual 363
C53000-G7040-C015-1, Edition 11.2019