Logic of the Function
[lo_7SR5_function47logicdiagram, 1, en_US]
Figure 5-11
Logic Diagram: 47 Sequence Overvoltage Protection
Application and Setting Notes
Parameter: 47 Common > UV Guard Setting
Default setting: 5 V
Voltage elements can be blocked if all phase voltages fall below the setting.
5.9.3
5.9.4
Protection and Automation Functions
5.9 47 Sequence Overvoltage Protection
194 Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019