37 Undercurrent Protection – Phase
Overview of Functions
Phase undercurrent protection is used to :
Detect loss of current flow after the primary circuit‑breaking device is opened
Detect the loss of loads e.g. this could indicate loss of cooling capacity
Detect and protect pumps from running idle
Structure of the Function
The undercurrent function elements have group dependent settings. These settings can be different in each
settings group – group numbers (Gn) 1 to 4.
This function corresponds to the logical node A37PTUC* in IEC 61850.
The function monitors the primary system using the 3 phase current inputs e.g. CT1/2/3.
Function operation is selected to Any or All phases.
Blocking of the Stage
When a binary input configured as Inhibit 37-n is operated, the picked up relevent function element will
reset.
5.5
5.5.1
5.5.2
Protection and Automation Functions
5.5 37 Undercurrent Protection – Phase
Reyrolle 7SR5, Transformer Protection Device, Device Manual 171