Analogue Inputs
The device functionality is dependent on the analogue input configuration.
7SR542 devices are used with 2-winding transformers. These have 8 CT inputs and optionally 4 VT inputs.
7SR543 devices are used with 2 of 3-winding transformers. These have 12 CT inputs and optionally 4 VT
inputs.
The measuring inputs (current and voltage inputs) for each function are parametrized in the Device
Configuration > CT/VT settings menu, see 3.3 CT and VT Inputs .
Typical analogue input connections for a 7SR5421 two winding transformer protection device is summarized
in Figure 2-1.
[dw_7SR5_7SR54DeviceAnalogueInputConnections, 1, en_US]
Figure 2-1 7SR54 Device Analogue Input Connections
The analogue input configuration for a 7SR5420 transformer device is summarized in Figure 2-2.
[dw_7SR5_7SR5420DeviceCTVTInputConfiguration, 1, en_US]
Figure 2-2 7SR5420 Device CT/VT Input Configuration
The analogue input configuration for a 7SR5421 transformer device is summarized in Figure 2-3.
2.2
Basic Structure of the Device Functionality
2.2 Analogue Inputs
Reyrolle 7SR5, Transformer Protection Device, Device Manual 27
C53000-G7040-C015-1, Edition 11.2019