A24ITPVPH1.Health
Information
Device Healthy 0 1
A24ITPVPH*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A24ITPVPH*.Op
Information
24IT-1 Operated 0 1
A24ITPVPH*.Op.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
A24ITPVPH*.Str
Information
24IT-1 Pickup 0 1
A24ITPVPH*.Str.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
Information List
Input/Output Matrix
General
Pickup
User Logic Type IEC
60870-5-1
03
DNP3 MODBUS
RTU
Inhibit 24DT-n Inhibit 24DT-n Input
24DT-n 24DT-n Operated Output Y Y Y
24DT-n
Pickup
24DT-n Pickup Output
Inhibit 24IT-1 Inhibit 24IT-1 Input
24IT-1 24IT-1 Operated Output Y Y Y
24IT-1
Pickup
24IT-1 Pickup Output
The complete serial protocol information list containing the DNP3, IEC 60870-5-103, and Modbus RTU data
information for the configured device can be generated using the Export Report feature in the Reydisp
Manager 2 tool, Serial Comms & Events.
5.2.7
Protection and Automation Functions
5.2 24 Overexcitation Protection
Reyrolle 7SR5, Transformer Protection Device, Device Manual 157
C53000-G7040-C015-1, Edition 11.2019