IEC 61850 Functional Information Mapping
Protection LLN0 (PROT/LLN0)
LLN0.Mod
Information
Device Ready 0 1 1
Out Of Service Mode x 1 0
LLN0.Mod.stVal 5 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
LLN0.Health
Information
Device Healthy 0 1
LLN0.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
LLN0.SGCB
Information
Active SettingGroup Group 1 to 4
LLN0.SGCB.ActSG Value
Device (LPHD1)
LPHD1.Proxy
Information
Reset Device 0 1
PTOC*.Health.stVal 1 0
3.2.6
Device Functionality
3.2 Device Configuration
Reyrolle 7SR5, Transformer Protection Device, Device Manual 55