EasyManua.ls Logo

Siemens Reyrolle 7SR5 - Page 376

Siemens Reyrolle 7SR5
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Single Point GGIO Control Elements (Normal Security) (SPDONSGGIO1, SPDONSGGIO2, SPDONSGGIO3,
SPDONSGGIO4)
SPDONSGGIO*.Mod
Information
Reset Device x
SPDONSGGIO*.Mod.stVal 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
SPDONSGGIO*.Health
Information
Device Healthy 0 1
SPDONSGGIO*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
SPDONSGGIO*.SPCSO
Information
SPDONS (Off/Open) 1 -
SPDONS (On/Close) - 1
SPDONSGGIO*.SPCSO.ctlVal 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value ON: 1
OFF: 0
Information
SPDONS Status (On/Closed) 0 1
SPDONSGGIO*.SPCSO.stVal 0 1
Control Functions
7.1 Device Control Functions
376 Reyrolle 7SR5, Transformer Protection Device, Device Manual