Q0XCBR*.BlkOpn
Information
CB Control Open Block 0 1
Q0XCBR*.BlkOpn.stVal 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
Q0XCBR*.BlkOpCnt
Information Measurand Value
CB Operations Counter Q0XCBR*.OpCnt.stVal 0 to 10000
Q0XCBR*.Pos
Information
CB Status Open 0 1 0 1
CB Status Closed 0 0 1 1
Q0XCBR*.Pos.stVal 00 01 10 11
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value INTERMEDIATE STATE: 00
OFF: 01
ON: 10
INVALID STATE: 11
Q0XCBR*.SumSwARs1
Information
Measurand Value
CB Wear PhA Q0XCBR*. SumSwARs1.stVal 0 to 10000
Q0XCBR*.SumSwARs2
Information
Measurand Value
CB Wear PhB Q0XCBR*. SumSwARs2.stVal 0 to 10000
Q0XCBR*.SumSwARs3
Information
Measurand Value
CB Wear PhC Q0XCBR*. SumSwARs3.stVal 0 to 10000
Q0CSWI1.Mod
Information
Reset Device x
Q0CSWI1.Mod.stVal 1
Control Functions
7.2 52 Circuit-Breaker Control
Reyrolle 7SR5, Transformer Protection Device, Device Manual 389
C53000-G7040-C015-1, Edition 11.2019