EasyManua.ls Logo

Siemens Reyrolle 7SR5 - Page 471

Siemens Reyrolle 7SR5
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Current
(multi-
ples of
setting
)
Operate time t for various time constraints (s)
0.5 min 1 min 2 min 3 min 5 min 10 min 15 min 20 min 30 min 50 min 100
min
6 0.85 1.69 3.38 5.07 8.45 16.9 25.35 33.81 50.71 84.51 169.03
7 0.62 1.24 2.47 3.71 6.19 12.37 18.56 24.74 37.11 67.86 123.72
8 0.47 0.94 1.89 2.83 4.72 9.45 14.17 18.90 28.35 47.25 94.49
9 0.37 0.75 1.49 2.24 3.73 7.45 11.18 14.91 22.36 37.27 74.54
10 0.30 0.60 1.21 1.81 3.02 6.03 9.05 12.06 18.09 30.15 60.3
Technical Data
10.11 49 Thermal Overload Protection
Reyrolle 7SR5, Transformer Protection Device, Device Manual 471
C53000-G7040-C015-1, Edition 11.2019

Table of Contents

Other manuals for Siemens Reyrolle 7SR5

Related product manuals